Cummins C60D6 60kW Agricultural Spec Diesel Generator (1-Phase 120/240V) - PowerGen USA
Cummins C60D6 60kW Agricultural Spec Diesel Generator (1-Phase 120/240V) - PowerGen USA
Robust product design and testing - The generator is designed to operate under extreme environmental conditions. The generator is tested and certified per the latest EPA and UL standards.
Heavy duty engine - Rugged 4-cycle industrial diesel delivers reliable power and fast response to load changes.
Alternator - Several alternator sizes offer selectable motor starting capability with low reactance 2/3 pitch windings, low waveform distortion with non-linear loads and fault clearing short-circuit capability.
Control system - Provides total generator set system integration including automatic remote starting/stopping, precise frequency and voltage regulation, alarm and status message display, output metering, auto-shutdown at fault detection and NFPA 110 Level 1 compliance.
Cooling system - Standard cooling package provides reliable running at up to 50 °C (122 °F) ambient temperature. Coolant heaters also come standard on generator sets for starting well below freezing.
Battle Short Mode – This mode will allow the generator to override certain faults that would normally shut the generator down.
Flexible exercise mode - The innovative, flexible exercise mode enables the generator to exercise at a time, frequency and duration that suits the customer's preference reducing unnecessary fuel consumption, emissions and noise.
Self-diagnostics and easy service - The generator is equipped with Cummins PowerCommand® electronic control to provide industry-leading self-diagnostic capabilities. In addition, critical components of the generator are designed to ensure service and preventive maintenance can be completed in a short period of time.
Weight, size, and sound level
Weight: 3915 lbs. (1776 kg)2
Size: Length 143.0 in (3621 mm), width 40.0 in (1016 mm), height 72.0 in (1836 mm)
Sound: 71.3 dB(A) at 23 ft. (7 m) with sound level 2 enclosure
|
|
Standby 60 Hz |
|
Model |
Model Number |
KW |
KVA |
C60D6 |
A060A345 |
60 |
60 |
C80D6C |
A061T469 |
80 |
80 |
C100D6C |
A061T471 |
100 |
100 |
C125D6D |
A060A344 |
125 |
125 |
C150D6D |
A061T474 |
150 |
150 |
C175D6D |
A061T476 |
175 |
175 |
C200D6D |
A061T477 |
200 |
200 |
SPECIFICATIONS
Model |
C60 D6 |
C80 D6C |
C100 D6C |
C125 D6D |
C150 D6D |
C175 D6D |
C200 D6D |
|
Controller |
PowerCommand 1.1 |
|||||||
Operational temp. range |
-40 F to +122 F |
|||||||
Circuit Breaker |
250 |
400 |
600 |
600 |
800 |
800 |
800 |
|
Governor reg. class |
ISO 8528 Part 1 Class G3 |
|||||||
Voltage regulation, no load to full load |
± 1.0% |
|||||||
Random voltage variation |
± 1.0% |
|||||||
Frequency regulation |
Isochronous |
|||||||
Random freq. variation |
± 0.5% |
|||||||
Radio frequency emissions compliance |
FCC code title 47 part 15 class A and B |
Engine SPecifications
Model |
C60 D6 |
C80 D6C |
C100 D6C |
C125 D6D |
C150 D6D |
C175 D6D |
C200 D6D |
||
Design |
QSB3.3 |
QSB5 |
QSB7 |
||||||
Displacement |
3.26 L (199 in3 ) |
4.5 L (272 in3 ) |
6.69 L (408 in3 ) |
||||||
Cylinder block |
Cast iron, in-line |
||||||||
Battery capacity (at ambient temperature of 0C (32 F) |
850 amps |
2x 850 amps |
|||||||
Battery charging alternator |
50 amps |
100 amps |
100 amps |
||||||
Starting voltage |
12-volt, negative ground |
2x 12-volt, negative ground |
|||||||
Lube oil filter type(s) |
Spin-on with relief value |
||||||||
Standard cooling system |
High ambient radiator |
||||||||
Rated speed |
1800rpm |
Alternator Specifications
Model |
C60 D6 |
C80 D6C |
C100 D6C |
C125 D6D |
C150 D6D |
C175 D6D |
C200 D6D |
Design |
Brushless, 4 pole, drip proof, revolving field |
||||||
Stator |
2/3 pitch |
||||||
Rotor |
Direct coupled, flexible disc |
||||||
Insulation system |
Class H per NEMA MG1-1.65 |
||||||
Standard temp. rise |
120 ºC (248 °F) Standby |
||||||
Exciter type |
Torque match (shunt) with PMG as option |
||||||
Alternator cooling |
Direct drive centrifugal blower |
||||||
AC waveform Total Harmonic Distortion (THDV) |
< 5% no load to full linear load, < 3% for any single harmonic |
||||||
Telephone Influence Factor (TIF) |
< 50 per NEMA MG1-22.43 |
||||||
Telephone Harmonic Factor (THF) |
< 3% |
Accessories
- Battery heater kit
- Audible alarm
- Engine oil heater
- Enclosure Sound Level 1 & 2
- Remote control displays
- Battery charger – stand-alone,12 V
- Auxiliary output relays (2)
- Circuit breakers
- Auxiliary configurable signal inputs (8) and relay outputs (8)
- Remote monitoring device – PowerCommand 500/550
- Annunciator – RS485
- Base barrier – elevated generator sets
- Alternator heater
Model |
Dim “A” mm (in.) |
Dim “B” mm (in.) |
Dim “C” mm (in.) |
Set weight*wet kg (lbs.) |
C60 D6 |
2235 (88) |
864 (34) |
1118 (44) |
771 (1700) |
C80 D6C |
2489 (98) |
965 (38) |
1321 (52) |
1054 (2324) |
C100 D6C |
1106 (2439) |
|||
C125 D6D |
2867 (113) |
1016 (40) |
1415 (56) |
1173 (2586) |
C150 D6D |
1390 (3064) |
|||
C175 D6D |
1442 (3179) |
|||
C200 D6D |
1583 (3491) |