Robust product design and testing - The Cummins 125kw generator is designed to operate under extreme environmental conditions. The generator is tested and certified per the latest EPA and UL standards, ensuring reliability in the toughest environments.
Heavy-duty engine - The rugged 4-cycle industrial diesel engine delivers reliable power and fast response to load changes, making this 125kw diesel generator perfect for a wide range of applications.
Alternator - Several alternator sizes offer selectable motor starting capability with low reactance 2/3 pitch windings, ensuring low waveform distortion with non-linear loads and fault-clearing short-circuit capability for optimal performance.
Control system - This generator’s control system provides total generator set system integration, including automatic remote starting/stopping, precise frequency and voltage regulation, alarm and status message display, output metering, auto-shutdown at fault detection, and NFPA 110 Level 1 compliance.
Cooling system - The standard cooling package ensures reliable operation at ambient temperatures up to 50°C (122°F). Coolant heaters also come standard on the Cummins C125 D6D generator for easy starting well below freezing.
Battle Short Mode – This feature allows the generator to override certain faults that would normally cause a shutdown, ensuring continuous operation when critical power is needed.
Flexible exercise mode - The innovative flexible exercise mode allows the generator to exercise at a time, frequency, and duration that suits the customer's preference, reducing unnecessary fuel consumption, emissions, and noise.
Self-diagnostics and easy service - The generator is equipped with Cummins PowerCommand® electronic control for industry-leading self-diagnostic capabilities. In addition, critical components are designed for quick service and preventive maintenance, ensuring long-term performance of your 125kw generator.
Weight, size, and sound level
Weight: 3915 lbs. (1776 kg)2
Size: Length 143.0 in (3621 mm), width 40.0 in (1016 mm), height 72.0 in (1836 mm)
Sound: 71.3 dB(A) at 23 ft. (7 m) with sound level 2 enclosure
|
|
Standby 60 Hz |
|
Model |
Model Number |
KW |
KVA |
C60D6 |
A060A345 |
60 |
60 |
C80D6C |
A061T469 |
80 |
80 |
C100D6C |
A061T471 |
100 |
100 |
C125D6D |
A060A344 |
125 |
125 |
C150D6D |
A061T474 |
150 |
150 |
C175D6D |
A061T476 |
175 |
175 |
C200D6D |
A061T477 |
200 |
200 |
SPECIFICATIONS
Model |
C60 D6 |
C80 D6C |
C100 D6C |
C125 D6D |
C150 D6D |
C175 D6D |
C200 D6D |
|
Controller |
PowerCommand 1.1 |
|||||||
Operational temp. range |
-40 F to +122 F |
|||||||
Circuit Breaker |
250 |
400 |
600 |
600 |
800 |
800 |
800 |
|
Governor reg. class |
ISO 8528 Part 1 Class G3 |
|||||||
Voltage regulation, no load to full load |
± 1.0% |
|||||||
Random voltage variation |
± 1.0% |
|||||||
Frequency regulation |
Isochronous |
|||||||
Random freq. variation |
± 0.5% |
|||||||
Radio frequency emissions compliance |
FCC code title 47 part 15 class A and B |
Engine SPecifications
Model |
C60 D6 |
C80 D6C |
C100 D6C |
C125 D6D |
C150 D6D |
C175 D6D |
C200 D6D |
||
Design |
QSB3.3 |
QSB5 |
QSB7 |
||||||
Displacement |
3.26 L (199 in3 ) |
4.5 L (272 in3 ) |
6.69 L (408 in3 ) |
||||||
Cylinder block |
Cast iron, in-line |
||||||||
Battery capacity (at ambient temperature of 0C (32 F) |
850 amps |
2x 850 amps |
|||||||
Battery charging alternator |
50 amps |
100 amps |
100 amps |
||||||
Starting voltage |
12-volt, negative ground |
2x 12-volt, negative ground |
|||||||
Lube oil filter type(s) |
Spin-on with relief value |
||||||||
Standard cooling system |
High ambient radiator |
||||||||
Rated speed |
1800rpm |
Alternator Specifications
Model |
C60 D6 |
C80 D6C |
C100 D6C |
C125 D6D |
C150 D6D |
C175 D6D |
C200 D6D |
Design |
Brushless, 4 pole, drip proof, revolving field |
||||||
Stator |
2/3 pitch |
||||||
Rotor |
Direct coupled, flexible disc |
||||||
Insulation system |
Class H per NEMA MG1-1.65 |
||||||
Standard temp. rise |
120 ºC (248 °F) Standby |
||||||
Exciter type |
Torque match (shunt) with PMG as option |
||||||
Alternator cooling |
Direct drive centrifugal blower |
||||||
AC waveform Total Harmonic Distortion (THDV) |
< 5% no load to full linear load, < 3% for any single harmonic |
||||||
Telephone Influence Factor (TIF) |
< 50 per NEMA MG1-22.43 |
||||||
Telephone Harmonic Factor (THF) |
< 3% |
Accessories
- Battery heater kit
- Audible alarm
- Engine oil heater
- Enclosure Sound Level 1 & 2
- Remote control displays
- Battery charger – stand-alone,12 V
- Auxiliary output relays (2)
- Circuit breakers
- Auxiliary configurable signal inputs (8) and relay outputs (8)
- Remote monitoring device – PowerCommand 500/550
- Annunciator – RS485
- Base barrier – elevated generator sets
- Alternator heater
Model |
Dim “A” mm (in.) |
Dim “B” mm (in.) |
Dim “C” mm (in.) |
Set weight*wet kg (lbs.) |
C60 D6 |
2235 (88) |
864 (34) |
1118 (44) |
771 (1700) |
C80 D6C |
2489 (98) |
965 (38) |
1321 (52) |
1054 (2324) |
C100 D6C |
1106 (2439) |
|||
C125 D6D |
2867 (113) |
1016 (40) |
1415 (56) |
1173 (2586) |
C150 D6D |
1390 (3064) |
|||
C175 D6D |
1442 (3179) |
|||
C200 D6D |
1583 (3491) |