Cummins C175 D6D 175kW Agricultural Spec Diesel Generator (1-Phase 120/240V) - PowerGen USA
Cummins C175 D6D 175kW Agricultural Spec Diesel Generator (1-Phase 120/240V) - PowerGen USA
Robust product design and testing - The 175kw generator is designed to operate under extreme environmental conditions. The generator is tested and certified per the latest EPA and UL standards, ensuring reliable performance even in tough environments.
Heavy duty engine - Rugged 4-cycle industrial diesel delivers reliable power and fast response to load changes, making the 175 kw diesel generator suitable for various applications.
Alternator - Several alternator sizes offer selectable motor starting capability with low reactance 2/3 pitch windings, low waveform distortion with non-linear loads, and fault-clearing short-circuit capability, ensuring top performance from the 175 kw generator.
Control system - Provides total generator set system integration, including automatic remote starting/stopping, precise frequency and voltage regulation, alarm and status message display, output metering, auto-shutdown at fault detection, and NFPA 110 Level 1 compliance, which ensures reliability for the 175 kw generator in mission-critical situations.
Cooling system - The standard cooling package provides reliable running at up to 50°C (122°F) ambient temperature. Coolant heaters also come standard on 175 kw diesel generator sets for starting well below freezing, ensuring seamless operation in all weather conditions.
Battle Short Mode – This mode allows the 175 kw generator to override certain faults that would normally shut the generator down, ensuring continuous operation when necessary.
Flexible exercise mode - The innovative, flexible exercise mode enables the 175 kw generator to exercise at a time, frequency, and duration that suits the customer's preference, reducing unnecessary fuel consumption, emissions, and noise.
Self-diagnostics and easy service - The generator is equipped with Cummins PowerCommand® electronic control, providing industry-leading self-diagnostic capabilities. In addition, critical components of the 175kw generator are designed to ensure service and preventive maintenance can be completed in a short period of time.
Weight, size, and sound level
Weight: 3915 lbs. (1776 kg)2
Size: Length 143.0 in (3621 mm), width 40.0 in (1016 mm), height 72.0 in (1836 mm)
Sound: 71.3 dB(A) at 23 ft. (7 m) with sound level 2 enclosure
|
|
Standby 60 Hz |
|
Model |
Model Number |
KW |
KVA |
C60D6 |
A060A345 |
60 |
60 |
C80D6C |
A061T469 |
80 |
80 |
C100D6C |
A061T471 |
100 |
100 |
C125D6D |
A060A344 |
125 |
125 |
C150D6D |
A061T474 |
150 |
150 |
C175D6D |
A061T476 |
175 |
175 |
C200D6D |
A061T477 |
200 |
200 |
SPECIFICATIONS
Model |
C60 D6 |
C80 D6C |
C100 D6C |
C125 D6D |
C150 D6D |
C175 D6D |
C200 D6D |
|
Controller |
PowerCommand 1.1 |
|||||||
Operational temp. range |
-40 F to +122 F |
|||||||
Circuit Breaker |
250 |
400 |
600 |
600 |
800 |
800 |
800 |
|
Governor reg. class |
ISO 8528 Part 1 Class G3 |
|||||||
Voltage regulation, no load to full load |
± 1.0% |
|||||||
Random voltage variation |
± 1.0% |
|||||||
Frequency regulation |
Isochronous |
|||||||
Random freq. variation |
± 0.5% |
|||||||
Radio frequency emissions compliance |
FCC code title 47 part 15 class A and B |
Engine SPecifications
Model |
C60 D6 |
C80 D6C |
C100 D6C |
C125 D6D |
C150 D6D |
C175 D6D |
C200 D6D |
||
Design |
QSB3.3 |
QSB5 |
QSB7 |
||||||
Displacement |
3.26 L (199 in3 ) |
4.5 L (272 in3 ) |
6.69 L (408 in3 ) |
||||||
Cylinder block |
Cast iron, in-line |
||||||||
Battery capacity (at ambient temperature of 0C (32 F) |
850 amps |
2x 850 amps |
|||||||
Battery charging alternator |
50 amps |
100 amps |
100 amps |
||||||
Starting voltage |
12-volt, negative ground |
2x 12-volt, negative ground |
|||||||
Lube oil filter type(s) |
Spin-on with relief value |
||||||||
Standard cooling system |
High ambient radiator |
||||||||
Rated speed |
1800rpm |
Alternator Specifications
Model |
C60 D6 |
C80 D6C |
C100 D6C |
C125 D6D |
C150 D6D |
C175 D6D |
C200 D6D |
Design |
Brushless, 4 pole, drip proof, revolving field |
||||||
Stator |
2/3 pitch |
||||||
Rotor |
Direct coupled, flexible disc |
||||||
Insulation system |
Class H per NEMA MG1-1.65 |
||||||
Standard temp. rise |
120 ºC (248 °F) Standby |
||||||
Exciter type |
Torque match (shunt) with PMG as option |
||||||
Alternator cooling |
Direct drive centrifugal blower |
||||||
AC waveform Total Harmonic Distortion (THDV) |
< 5% no load to full linear load, < 3% for any single harmonic |
||||||
Telephone Influence Factor (TIF) |
< 50 per NEMA MG1-22.43 |
||||||
Telephone Harmonic Factor (THF) |
< 3% |
Accessories
- Battery heater kit
- Audible alarm
- Engine oil heater
- Enclosure Sound Level 1 & 2
- Remote control displays
- Battery charger – stand-alone,12 V
- Auxiliary output relays (2)
- Circuit breakers
- Auxiliary configurable signal inputs (8) and relay outputs (8)
- Remote monitoring device – PowerCommand 500/550
- Annunciator – RS485
- Base barrier – elevated generator sets
- Alternator heater
Model |
Dim “A” mm (in.) |
Dim “B” mm (in.) |
Dim “C” mm (in.) |
Set weight*wet kg (lbs.) |
C60 D6 |
2235 (88) |
864 (34) |
1118 (44) |
771 (1700) |
C80 D6C |
2489 (98) |
965 (38) |
1321 (52) |
1054 (2324) |
C100 D6C |
1106 (2439) |
|||
C125 D6D |
2867 (113) |
1016 (40) |
1415 (56) |
1173 (2586) |
C150 D6D |
1390 (3064) |
|||
C175 D6D |
1442 (3179) |
|||
C200 D6D |
1583 (3491) |